ConsoliDator
®
Multi-Channel Controller
Instruction Manual
ConsoliDator 8 ConsoliDator 4
Eight 4-20 mA Inputs Four 4-20 mA Inputs
Eight 24 VDC @ 20 mA Four 24 VDC @ 20 mA
Two 4-20 mA Outputs Four 4-20 mA Outputs
Features and Highlights
Nine Form C 10 A Relays Powered from AC or DC
Four Pulse Inputs 32-Point Linearization
Four Digital Inputs RS-232 Modbus
®
RTU
Panel or wall mount Square Root Function
Sum and Difference
Functions
FREE Programming &
data logging software
PC
Software
Included!
Vue de la page 0
1 2 3 4 5 6 ... 55 56

Résumé du contenu

Page 1 - ConsoliDator

PRECISION DIGITAL CORPORATION89 October Hill Road • Holliston MA 01746 USA Tel (800) 343-1001 • Fax (508) 655-8990 www.predig.com ConsoliDator® Mult

Page 2 - Visit our Web Site

ConsoliDator Multi-Channel ControllerInstruction Manual 10 4-20 mA Transmitter Outputs OUTPUT RANGE 4.00 to 20.00 mA CALIBRATION Factory calibrated

Page 3 - ORDERING INFORMATION

ConsoliDator Multi-Channel ControllerInstruction Manual 11 SAFETY INFORMATION ! CAUTION: Read complete instructions prior to installation and operat

Page 4

ConsoliDator Multi-Channel ControllerInstruction Manual 12 INSTALLATION Unpacking Remove the instrument from its box. Inspect the packaging and conte

Page 5

ConsoliDator Multi-Channel ControllerInstruction Manual 13 Panel Mounting (For PD981 & PD941 Models)  Obtain four #8 (M4) screws and nuts.  Ob

Page 6 - Table of Figures

ConsoliDator Multi-Channel ControllerInstruction Manual 14 Connections Connections are made to removable screw terminal connectors and a DB9 male seri

Page 7 - SPECIFICATIONS

ConsoliDator Multi-Channel ControllerInstruction Manual 15 Input Signal Connections Input signal connections are made to terminal connectors, which ar

Page 8 - Digital Inputs

ConsoliDator Multi-Channel ControllerInstruction Manual 16 Flow Meter Pulse Input Connections Flow Meter Pulse Inputs are wired to two-terminal connec

Page 9

ConsoliDator Multi-Channel ControllerInstruction Manual 17 Analog Output Connections The following figures show examples for 4-20 mA transmitter outpu

Page 10 - Instruction Manual

ConsoliDator Multi-Channel ControllerInstruction Manual 18 Relay Connections Relay connections are made to three-terminal connectors labeled on the si

Page 11 - SAFETY INFORMATION

ConsoliDator Multi-Channel ControllerInstruction Manual 19 Serial Communication Connections A DB9 male connector is the port for RS-232 serial communi

Page 12 - 8.00" (203 mm)

ConsoliDator Multi-Channel ControllerInstruction Manual 2 Visit our Web Site http://www.predig.com/ Disclaimer The information contained

Page 13 - Panel Mounting

ConsoliDator Multi-Channel ControllerInstruction Manual 20 Figure 16. External Keypad Connections NAVIGATING AND EDITING The device displays various s

Page 14 - Connections

ConsoliDator Multi-Channel ControllerInstruction Manual 21 SETUP AND PROGRAMMING There is no need to recalibrate the instrument when first received f

Page 15 - Input Signal Connections

ConsoliDator Multi-Channel ControllerInstruction Manual 22 Main Setup Menu The main setup menu is the access point during the programming process for

Page 16 - Switch Contact

ConsoliDator Multi-Channel ControllerInstruction Manual 23 Backlight Selecting [YES] under Save BL automatically turns the backlight off if no buttons

Page 17 - ANALOG OUTPUT

ConsoliDator Multi-Channel ControllerInstruction Manual 24 Configuring 4-20 mA Inputs The Analog Input setup screen is used to configure the 4-20 mA a

Page 18 - Relay Connections

ConsoliDator Multi-Channel ControllerInstruction Manual 25 Input Scaling & Math Functions The ConsoliDator is capable of various functions for sca

Page 19 - External Keypad Connections

ConsoliDator Multi-Channel ControllerInstruction Manual 26 Square Root Square root mode refers to 2-point scaling with square root extraction typicall

Page 20 - SETUP AUTO ACK NEXT

ConsoliDator Multi-Channel ControllerInstruction Manual 27 Exponent Exponent mode refers to 2-point scaling with programmable exponent (programmable r

Page 21 - Press SETUP key to begin

ConsoliDator Multi-Channel ControllerInstruction Manual 28 Integration Mode Integration mode is able to totalize from any 4-20 mA channel over a time

Page 22 - Main Setup Menu

ConsoliDator Multi-Channel ControllerInstruction Manual 29 Multi-Point Linearization Multi-Point Linearization must be configured using a PC and suppl

Page 23

ConsoliDator Multi-Channel ControllerInstruction Manual 3 INTRODUCTION The ConsoliDator is an easy to use multiple-channel controller. It accepts 4-20

Page 24 - Configuring 4-20 mA Inputs

ConsoliDator Multi-Channel ControllerInstruction Manual 30 Setting Flow Meter Pulse Inputs The Flow Meter menu is used to configure a flow meter pulse

Page 25

ConsoliDator Multi-Channel ControllerInstruction Manual 31 Programming Relays Each relay has an Alarm Setup menu used to program its functions. Functi

Page 26

ConsoliDator Multi-Channel ControllerInstruction Manual 32 Multi-Channel High or Low Alarm Modes Multi-Channel High or Low modes are used as an alarm

Page 27

ConsoliDator Multi-Channel ControllerInstruction Manual 33 High or Low Pulse Alarm Modes Pulse Modes are used to generate an on/off continuous pulsing

Page 28

ConsoliDator Multi-Channel ControllerInstruction Manual 34 Trigger Alarm Mode Select Trigger mode to pulse the relay once each time the total from a f

Page 29 - Sensor Input Setup

ConsoliDator Multi-Channel ControllerInstruction Manual 35 Plunger Lift by Differential Pressure Mode Select [PLUNGER LIFT: DP] from Alarm Mode option

Page 30 - Setting Flow Meter Pulse

ConsoliDator Multi-Channel ControllerInstruction Manual 36 Lead-Lag Modes (Pump Alternation Control) Lead-Lag modes are used to operate up to 9 relays

Page 31 - Programming Relays

ConsoliDator Multi-Channel ControllerInstruction Manual 37 Lead-Lag Override Function Lead-Lag mode supports an override function, which allows up to

Page 32 - EDIT EXIT

ConsoliDator Multi-Channel ControllerInstruction Manual 38 Linear Pulse Width Modulation Mode Linear PWM Mode is used to create an on/off pulse signal

Page 33 - Set Point Reached

ConsoliDator Multi-Channel ControllerInstruction Manual 39 Proportional Plus Integral Pulse Width Modulation Mode PWM PI Control Mode is used to creat

Page 34

ConsoliDator Multi-Channel ControllerInstruction Manual 4 TABLE OF CONTENTS INTRODUCTION -----------------------------------------------------------

Page 35

ConsoliDator Multi-Channel ControllerInstruction Manual 40 Setting 4-20 mA Outputs The Analog Output menu is used to configure the 4-20 mA outputs. Ea

Page 36 - (Pump Alternation Control)

ConsoliDator Multi-Channel ControllerInstruction Manual 41 OPERATION Viewing Screens The instrument displays various screens with bargraphs, numerical

Page 37

ConsoliDator Multi-Channel ControllerInstruction Manual 42 Multiple Channel Operation Screen To the right is an example of a multiple channel operatio

Page 38 - Modulation Mode

ConsoliDator Multi-Channel ControllerInstruction Manual 43 Single Flow Meter Pulse Input Operation Screen For each flow meter pulse input channel, the

Page 39 - Pulse Width Modulation Mode

ConsoliDator Multi-Channel ControllerInstruction Manual 44 Analog Input Numeric Screen To the right is an example of an analog numeric summary screen

Page 40 - Setting 4-20 mA Outputs

ConsoliDator Multi-Channel ControllerInstruction Manual 45 Manual and Simulation Modes When manual mode is entered, all outputs are suspended or froze

Page 41 - OPERATION

ConsoliDator Multi-Channel ControllerInstruction Manual 46 Contrast Adjustment Control All ConsoliDators are adjusted at the factory for optimal viewi

Page 42

ConsoliDator Multi-Channel ControllerInstruction Manual 47 MODBUS® SERIAL COMMUNICATION The controller is equipped with serial communication capabilit

Page 43 - AUTOSETUP

ConsoliDator Multi-Channel ControllerInstruction Manual 48 Table 2. Analog Input Channels Register Addresses Address (offset from 40000) Description

Page 44

ConsoliDator Multi-Channel ControllerInstruction Manual 49 Table 3. Flow Meter Pulse Input Channels Register Addresses Address (offset from 40000) Des

Page 45 - Manual and Simulation Modes

ConsoliDator Multi-Channel ControllerInstruction Manual 5 Tx Delay --------------------------------------------------------------------------------- 2

Page 46 - Contrast Adjustment Control

ConsoliDator Multi-Channel ControllerInstruction Manual 50 Table 5. Relay Channels Register Addresses Address (offset from 40000) Description Data Ty

Page 47 - SERIAL COMMUNICATION

ConsoliDator Multi-Channel ControllerInstruction Manual 51 Table 6. Analog Inputs, Flow meter, and Relay State Summary Address (offset from 40000) De

Page 48

ConsoliDator Multi-Channel ControllerInstruction Manual 52 CONSOLIDATOR MONITOR SOFTWARE Each ConsoliDator is shipped with PC software on CD-ROM, whic

Page 49

ConsoliDator Multi-Channel ControllerInstruction Manual 53 Data Logging The software supports logging input readings to a comma separated value file (

Page 50

ConsoliDator Multi-Channel ControllerInstruction Manual 54 OVERALL DIMENSIONS 3.0" (76mm)8.0" (203mm)8.75" (222mm) Figure 22. PD980 &a

Page 51

ConsoliDator Multi-Channel ControllerInstruction Manual 55 TROUBLESHOOTING TIPS Symptom Check/Action No display, or only backlight is visible, but ou

Page 52 - Installing Software

ConsoliDator Multi-Channel ControllerInstruction Manual LIM980_F v3.1.1 & Up 05/12 How to Contact Precision Digital  For Technical Support pl

Page 53 - Programming Through Software

ConsoliDator Multi-Channel ControllerInstruction Manual 6 Table of Figures Figure 1. Wall Mount Dimensions (PD980 & PD940) ...

Page 54 - OVERALL DIMENSIONS

ConsoliDator Multi-Channel ControllerInstruction Manual 7 SPECIFICATIONS Except where noted all specifications apply to operation at +25°C (77°F.) Gen

Page 55 - TROUBLESHOOTING TIPS

ConsoliDator Multi-Channel ControllerInstruction Manual 8 4-20 mA Analog Inputs INPUT 4-20 mA; minimum span of 1 mA ACCURACY ±0.03% of span 1 count

Page 56 - LIM980_F

ConsoliDator Multi-Channel ControllerInstruction Manual 9 Relays RATING SPDT (form C); rated 10 A @ 120/240 VAC or 5 A @ 28 VDC resistive load; 1/3 H