PRECISION DIGITAL CORPORATION
89 October Hill Road • Holliston MA 01746 USA
Tel (800) 343-1001 • Fax (508) 655-8990
www.predig.com
PD6400 High Voltage
and Current Meter
Instruction Manual
(1) High Voltage and (1) High Current Input
Multiplication for Apparent Power Calculation
0-300 VAC or VDC Voltage Input
0-5 AAC or ADC Current Input
NEMA 4X, IP65 Front
85-265 VAC or 12/24 VDC Input Power Models
Large Dual-Line 6-Digit Display, 0.60" & 0.46"
Sunlight Readable SunBright Display Models
Programmable Display & Function Keys
2 or 4 Relays + Isolated 4-20 mA Output Options
External 4-Relay & Digital I/O Expansion Modules
USB, RS-232 & RS-485 Serial Communication Options
Modbus
®
RTU Communication Protocol Standard
Configure, Monitor, and Datalog from a PC with
Free MeterView
®
Pro Software
Vue de la page 0
1 2 3 4 5 6 ... 95 96

Résumé du contenu

Page 1 - PD6400 High Voltage

PRECISION DIGITAL CORPORATION 89 October Hill Road • Holliston MA 01746 USA Tel (800) 343-1001 • Fax (508) 655-8990 www.predig.com PD6400 High Volt

Page 2 - Registered Trademarks

Model PD6400 High Voltage & Current Meter Instruction Manual 10 ACCURACY ADC: 0.03% Full Scale ±1 count, AAC: 0.1% Full Scale ±1 count, VDC: 0.

Page 3 - Table of Contents

Model PD6400 High Voltage & Current Meter Instruction Manual 11 RELAY ASSIGNMENT Each relay independently assigned to Ch-A, Ch-V, CH-P, or Modbus

Page 4

Model PD6400 High Voltage & Current Meter Instruction Manual 12 TEMPERATURE DRIFT 0.4 µA/°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 t

Page 5

Model PD6400 High Voltage & Current Meter Instruction Manual 13 COMPLIANCE INFORMATION Safety UL & c-UL LISTED USA & Canada UL 508 Indus

Page 6 - INTRODUCTION

Model PD6400 High Voltage & Current Meter Instruction Manual 14 Note: Testing was conducted on PD6000 Series meters installed through the covers

Page 7 - ORDERING INFORMATION

Model PD6400 High Voltage & Current Meter Instruction Manual 15 • Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm). Recommended minim

Page 8 - SPECIFICATIONS

Model PD6400 High Voltage & Current Meter Instruction Manual 16 MOUNTING DIMENSIONS Figure 3. Meter Dimensions - Side View Figure 4. Meter D

Page 9 - Voltage and Current Inputs

Model PD6400 High Voltage & Current Meter Instruction Manual 17 Configuration for 12 or 24 VDC Power Option Warning! Do not exceed voltage rati

Page 10

Model PD6400 High Voltage & Current Meter Instruction Manual 18 Connections All connections are made to removable screw terminal connectors locat

Page 11

Model PD6400 High Voltage & Current Meter Instruction Manual 19 Power Connections Power connections are made to a two-terminal connector labeled

Page 12

Model PD6400 High Voltage & Current Meter Instruction Manual 2 Disclaimer The information contained in this document is subject to change without

Page 13 - COMPLIANCE INFORMATION

Model PD6400 High Voltage & Current Meter Instruction Manual 20 Figure 9. DC Voltage Input Connections Current Input The following figures sho

Page 14 - INSTALLATION

Model PD6400 High Voltage & Current Meter Instruction Manual 21 Figure 12. DC Current Connections Current and Voltage Input The following figu

Page 15 - (1.5mm) Max Radius

Model PD6400 High Voltage & Current Meter Instruction Manual 22 Figure 14. AC Current Transformer and Voltage Connections Figure 15. DC Curre

Page 16 - MOUNTING DIMENSIONS

Model PD6400 High Voltage & Current Meter Instruction Manual 23 Modbus RTU Serial Communications Serial communications connection is made to an R

Page 17 - MAIN BOARD

Model PD6400 High Voltage & Current Meter Instruction Manual 24 Switching Inductive Loads The use of suppressors (snubbers) is strongly recommend

Page 18 - Connections

Model PD6400 High Voltage & Current Meter Instruction Manual 25 F4 Digital Input Connections A digital input, F4, is standard on the meter. This

Page 19 - Power Connections

Model PD6400 High Voltage & Current Meter Instruction Manual 26 External Relay, Analog Output, & Digital I/O Connections The relay, analog ou

Page 20

Model PD6400 High Voltage & Current Meter Instruction Manual 27 SETUP AND PROGRAMMING The meter is factory calibrated prior to shipment to read

Page 21

Model PD6400 High Voltage & Current Meter Instruction Manual 28 Front Panel Buttons and Status LED Indicators Button Symbol Description LED Sta

Page 22

Model PD6400 High Voltage & Current Meter Instruction Manual 29 Display Functions & Messages The following table shows the main menu function

Page 23 - Relay Connections

Model PD6400 High Voltage & Current Meter Instruction Manual 3 Table of Contents INTRODUCTION ---------------------------------------------------

Page 24 - Switching Inductive Loads

Model PD6400 High Voltage & Current Meter Instruction Manual 30 Display Parameter Action/Setting Description Little Lower display Assign the l

Page 25 - 4-20 mA Output Connections

Model PD6400 High Voltage & Current Meter Instruction Manual 31 Display Parameter Action/Setting Description d-Inty Display intensity Set dis

Page 26 - Interlock Relay Feature

Model PD6400 High Voltage & Current Meter Instruction Manual 32 Display Parameter Action/Setting Description On On Relay goes to alarm c

Page 27 - SETUP AND PROGRAMMING

Model PD6400 High Voltage & Current Meter Instruction Manual 33 Main Menu The main menu consists of the most commonly used functions: Reset, Cont

Page 28

Model PD6400 High Voltage & Current Meter Instruction Manual 34 Setting Numeric Values The numeric values are set using the Right and Up arrow bu

Page 29

Model PD6400 High Voltage & Current Meter Instruction Manual 35 Setting Up the Meter (setup) The Setup menu is used to select: 1. Input signal t

Page 30

Model PD6400 High Voltage & Current Meter Instruction Manual 36 Setting the Decimal Point (dEc pt) The decimal point may be set with up to f

Page 31

Model PD6400 High Voltage & Current Meter Instruction Manual 37 Setting the Input Calibration (InCal) It is very important to read the following

Page 32

Model PD6400 High Voltage & Current Meter Instruction Manual 38 Multi-Point Linearization (Linear) The process inputs may be calibrated or scaled

Page 33 - Main Menu

Model PD6400 High Voltage & Current Meter Instruction Manual 39 Scaling the Meter for Channel A (SCal-A) Scaling the Meter for Channel V (SCal

Page 34 - Setting Numeric Values

Model PD6400 High Voltage & Current Meter Instruction Manual 4 Setting the Input Calibration (InCal) ------------------------------------ 37 Mult

Page 35 - Setting Up the Meter (setup)

Model PD6400 High Voltage & Current Meter Instruction Manual 40 Error Message (Error) An error message indicates that the calibration or scaling

Page 36

Model PD6400 High Voltage & Current Meter Instruction Manual 41 Calibrating the Meter for Channel A (CAL-A) Calibrating the Meter for Channel

Page 37

Model PD6400 High Voltage & Current Meter Instruction Manual 42 Setting the Display Parameter & Intensity (dsplay) The Upper display (Big) ca

Page 38

Model PD6400 High Voltage & Current Meter Instruction Manual 43 Display Setup Menu After setting up the input and display, press the Menu button

Page 39

Model PD6400 High Voltage & Current Meter Instruction Manual 44 Setting the Input Units or Custom Tags (units) Enter the input unit or custom tag

Page 40

Model PD6400 High Voltage & Current Meter Instruction Manual 45 Setting the Relay Operation (relay) This menu is used to set up the assignment an

Page 41

Model PD6400 High Voltage & Current Meter Instruction Manual 46 Setting the Relay Assignment (asSign)

Page 42

Model PD6400 High Voltage & Current Meter Instruction Manual 47 Setting the Relay Action Operation of the relays is programmed in the Action menu

Page 43 - Display Setup Menu

Model PD6400 High Voltage & Current Meter Instruction Manual 48 Programming Set and Reset Points High alarm indication: program set point above r

Page 44

Model PD6400 High Voltage & Current Meter Instruction Manual 49 Relay and Alarm Operation Diagrams The following graphs illustrate the operation

Page 45

Model PD6400 High Voltage & Current Meter Instruction Manual 5 Scaling the 4-20 mA Analog Output (Aout) ---------------------------- 61 Reset Men

Page 46

Model PD6400 High Voltage & Current Meter Instruction Manual 50 Low Alarm Operation (Set < Reset) For Manual reset mode, ACK can be pressed a

Page 47 - Setting the Relay Action

Model PD6400 High Voltage & Current Meter Instruction Manual 51 High Alarm with Fail-Safe Operation (Set > Reset) Note: Relay coil is energi

Page 48 - Programming Time Delay

Model PD6400 High Voltage & Current Meter Instruction Manual 52 Low Alarm with Fail-Safe Operation (Set < Reset) Note: Relay coil is energiz

Page 49

Model PD6400 High Voltage & Current Meter Instruction Manual 53 Relay Sampling Operation When the signal crosses the set point, the relay trips

Page 50

Model PD6400 High Voltage & Current Meter Instruction Manual 54 Signal Loss or Loop Break Relay Operation The following graph shows the loop brea

Page 51

Model PD6400 High Voltage & Current Meter Instruction Manual 55 Time Delay Operation The following graphs show the operation of the time delay fu

Page 52

Model PD6400 High Voltage & Current Meter Instruction Manual 56 Relay Operation Details Overview The relay capabilities of the meter expand its u

Page 53 - Relay Sampling Operation

Model PD6400 High Voltage & Current Meter Instruction Manual 57 Front Panel LEDs The LEDs on the front panel provide status indication for the fo

Page 54 - Loop Break = On

Model PD6400 High Voltage & Current Meter Instruction Manual 58 Non-Latching Relay (Auto) Automatic reset only Condition LED Relay Normal Off O

Page 55 - Time Delay Operation

Model PD6400 High Voltage & Current Meter Instruction Manual 59 Latching Relay (Lt-Clr) Manual reset only after alarm condition has cleared Condi

Page 56 - Relay Operation Details

Model PD6400 High Voltage & Current Meter Instruction Manual 6 Table of Figures Figure 1. 1/8 DIN Panel Cutout Dimensions ...

Page 57 - Warning!

Model PD6400 High Voltage & Current Meter Instruction Manual 60 Pump Alternation Control Applications (Altern) Pump alternation control is not re

Page 58 - Latching Relay (LatcH)

Model PD6400 High Voltage & Current Meter Instruction Manual 61 Interlock Relay Operation Example Relays 1 & 2 are configured to energize (th

Page 59 - PDA1044 Digital I/O Module

Model PD6400 High Voltage & Current Meter Instruction Manual 62 Reset Menu (reset) The Reset menu is used to reset the maximum or minimum reading

Page 60 - 5 VDC GND

Model PD6400 High Voltage & Current Meter Instruction Manual 63 Setting Up the Password (pass) The Password menu is used for programming three le

Page 61

Model PD6400 High Voltage & Current Meter Instruction Manual 64 Making Changes to a Password Protected Meter If the meter is password protected,

Page 62 - Control Menu (Contrl)

Model PD6400 High Voltage & Current Meter Instruction Manual 65 Advanced Features Menu To simplify the setup process, functions not needed for mo

Page 63

Model PD6400 High Voltage & Current Meter Instruction Manual 66 Display Parameter Action/Setting No pts Number of points Set the number of li

Page 64

Model PD6400 High Voltage & Current Meter Instruction Manual 67 Display Parameter Action/Setting F4 F4 function Assign F4 function (digital in

Page 65 - Advanced Features Menu

Model PD6400 High Voltage & Current Meter Instruction Manual 68 Noise Filter (filter) The noise filter is available for unusually noisy signals t

Page 66

Model PD6400 High Voltage & Current Meter Instruction Manual 69 Rounding Feature (round) The rounding feature is used to give the user a steadier

Page 67

Model PD6400 High Voltage & Current Meter Instruction Manual 7 ORDERING INFORMATION Standard Models 85-265 VAC Model 12/24 VDC Model Options Inst

Page 68 - Noise Filter (filter)

Model PD6400 High Voltage & Current Meter Instruction Manual 70 Select Menu (SElect) The Select menu is used to select the number of linearizatio

Page 69 - Rounding Feature (round)

Model PD6400 High Voltage & Current Meter Instruction Manual 71 Multi-Point Linearization (Linear) The multi-point linearization can be used to

Page 70 - Select Menu (SElect)

Model PD6400 High Voltage & Current Meter Instruction Manual 72 Math Function (math) Within the Math menu is the power function, P = I*V, availab

Page 71

Model PD6400 High Voltage & Current Meter Instruction Manual 73 Analog Output Source The analog output source can be based on either of the input

Page 72 - Low-Flow Cutoff (CutofF)

Model PD6400 High Voltage & Current Meter Instruction Manual 74 Programmable Function Keys User Menu (user) The User menu allows the user to assi

Page 73

Model PD6400 High Voltage & Current Meter Instruction Manual 75 Display Description Display Description disabl Disable function key Rst Hi Res

Page 74

Model PD6400 High Voltage & Current Meter Instruction Manual 76 Internal Calibration (ICAL) The meter is factory calibrated prior to shipment to

Page 75

Model PD6400 High Voltage & Current Meter Instruction Manual 77 8. The display moves to the high input calibration (C Hi). Apply the high input

Page 76 - Internal Calibration (ICAL)

Model PD6400 High Voltage & Current Meter Instruction Manual 78 Error Message (Error) An error message indicates that the calibration or scaling

Page 77

Model PD6400 High Voltage & Current Meter Instruction Manual 79 Meter Copy Function (Copy) The Copy function is used to copy (or clone) all the s

Page 78

Model PD6400 High Voltage & Current Meter Instruction Manual 8 SPECIFICATIONS Except where noted all specifications apply to operation at +25°C.

Page 79 - Meter Copy Function (Copy)

Model PD6400 High Voltage & Current Meter Instruction Manual 80 1. Connect two meters using a PDA1200 meter copy cable. Warning! Using stand

Page 80

Model PD6400 High Voltage & Current Meter Instruction Manual 81 METER OPERATION The meter is capable of accepting two input channels (A and V) of

Page 81 - METER OPERATION

Model PD6400 High Voltage & Current Meter Instruction Manual 82 Function Keys Operation During operation, the programmable function keys operate

Page 82 - Maximum/Minimum Readings

Model PD6400 High Voltage & Current Meter Instruction Manual 83 TROUBLESHOOTING Due to the many features and functions of the meter, it’s possibl

Page 83 - TROUBLESHOOTING

Model PD6400 High Voltage & Current Meter Instruction Manual 84 Reset Meter to Factory Defaults When the parameters have been changed in a way th

Page 84

Model PD6400 High Voltage & Current Meter Instruction Manual 85 Factory Defaults & User Settings The following table shows the factory settin

Page 85

Model PD6400 High Voltage & Current Meter Instruction Manual 86 Parameter Display Default Setting User Setting Bypass, channel A bypass 0.2 By

Page 86

Model PD6400 High Voltage & Current Meter Instruction Manual 87 Parameter Display Default Setting User Setting Fail-safe relay 4 Fls 4 Off On

Page 87

Model PD6400 High Voltage & Current Meter Instruction Manual 88 Parameter Display Default Setting User Setting F2 function key F2 Upper Max &

Page 88

Model PD6400 High Voltage & Current Meter Instruction Manual 89 Alphabetical List of Display Functions & Messages Display Parameter Action/S

Page 89

Model PD6400 High Voltage & Current Meter Instruction Manual 9 POWER OPTIONS 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or jumper selectable 12/24

Page 90

Model PD6400 High Voltage & Current Meter Instruction Manual 90 Display Parameter Action/Setting Description Copy Copy Enter copy function CutofF

Page 91

Model PD6400 High Voltage & Current Meter Instruction Manual 91 Display Parameter Action/Setting Description Error Error Error, calibration not

Page 92

Model PD6400 High Voltage & Current Meter Instruction Manual 92 Display Parameter Action/Setting Description Lt-CLr Latching-cleared Set relay fo

Page 93

Model PD6400 High Voltage & Current Meter Instruction Manual 93 Display Parameter Action/Setting Description SCAL A Scale A Enter the Scale menu

Page 94 - Troubleshooting Tips

Model PD6400 High Voltage & Current Meter Instruction Manual 94 Troubleshooting Tips Symptom Check/Action No display at all Check power at power

Page 95

Model PD6400 High Voltage & Current Meter Instruction Manual 95 This Page Intentionally Left Blank

Page 96 - SFT106 Ver 3.200 & up

Model PD6400 High Voltage & Current Meter Instruction Manual LIM6400_A SFT106 Ver 3.200 & up 12/14 How to Contact Precision Digital • For Te